Catalogue 2021

www.incitefire.com.au for technical information 65 2 Simple 3 Step Set Up Max. overall length of the sampling pipe tube network Max. length from ASD to farthest sampling hole Max. number of sampling holes 75 m 40 m 6 Class A 75 m 40 m 8 Class B 75 m 40 m 12 Class C AS 7240.20 SEC-ASD-531 SEC-ASD-531 Aspirating Smoke Detector (including SSD 31) 1 Sampling pipe / Detector The SecuriRAS SEC-ASD-531 aspirating smoke detector is designed for smaller monitoring areas and for the easiest possible handling. The SEC-ASD-531 is equipped with a highly sensitive smoke sensor SSD 31 using a single sampling pipe network. The housing provides the option for two expansion modules. Commissioning and configuration is done directly on the device without any software tool. For planning the ASD PipeFlow software allows an optimized design of any installation. Technical data Mains voltage: Ambient temperature: Protection class: Dimensions (H x W x D): Case cover material: Case Colour: Weight: Standards: Maximum sampling pipe length: Monitoring area: Application: 14 to 30 V DC -10 °C to + 55 °C IP 54 195 x 290 x 140 mm ABS-Blend, UL 94-V0 Grey 1,95 kg AS 7240.20 75 metres 720 m2 Single IT racks, small tele-communications containers, elevator shafts, clean rooms, false ceilings etc. ASPIRATING SYSTEMS - Base Units SECURITON